ID

VAR-202504-1134


CVE

CVE-2025-30032


TITLE

Siemens'  telecontrol server basic  In  SQL  Injection vulnerability

Trust: 0.8

sources: JVNDB: JVNDB-2025-011789

DESCRIPTION

A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'UpdateDatabaseSettings' method. This could allow an authenticated remote attacker to bypass authorization controls, to read from and write to the application's database and execute code with "NT AUTHORITY\NetworkService" permissions. A successful attack requires the attacker to be able to access port 8000 on a system where a vulnerable version of the affected application is executed on. (ZDI-CAN-25921). Siemens' telecontrol server basic for, SQL There is an injection vulnerability.Information is obtained, information is tampered with, and service operation is interrupted. (DoS) It may be in a state. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.The specific flaw exists within the implementation of the UpdateDatabaseSettings method. The issue results from the lack of proper validation of a user-supplied string before using it to construct SQL queries. An attacker could leverage this vulnerability to disclose stored credentials, leading to further compromise. Siemens TeleControl Server Basic is an industrial remote controller of Siemens, Germany. Siemens TeleControl Server Basic versions prior to v3.1.2.2 have multiple SQL injection vulnerabilities that can be exploited by attackers to read and write the application's database, causing a denial of service and executing code in the operating system shell with limited "NT AUTHORITYNetworkService" permissions

Trust: 3.33

sources: NVD: CVE-2025-30032 // JVNDB: JVNDB-2025-011789 // ZDI: ZDI-25-390 // CNVD: CNVD-2025-08353 // CNVD: CNVD-2025-08398

IOT TAXONOMY

category:['ICS']sub_category: -

Trust: 1.2

sources: CNVD: CNVD-2025-08353 // CNVD: CNVD-2025-08398

AFFECTED PRODUCTS

vendor:siemensmodel:telecontrol server basicscope:ltversion:v3.1.2.2

Trust: 1.2

vendor:siemensmodel:telecontrol server basicscope:ltversion:3.1.2.2

Trust: 1.0

vendor:シーメンスmodel:telecontrol server basicscope:eqversion: -

Trust: 0.8

vendor:シーメンスmodel:telecontrol server basicscope: - version: -

Trust: 0.8

vendor:シーメンスmodel:telecontrol server basicscope:eqversion:3.1.2.2

Trust: 0.8

vendor:siemensmodel:telecontrol server basicscope: - version: -

Trust: 0.7

sources: ZDI: ZDI-25-390 // CNVD: CNVD-2025-08353 // CNVD: CNVD-2025-08398 // JVNDB: JVNDB-2025-011789 // NVD: CVE-2025-30032

CVSS

SEVERITY

CVSSV2

CVSSV3

productcert@siemens.com: CVE-2025-30032
value: HIGH

Trust: 1.0

OTHER: JVNDB-2025-011789
value: HIGH

Trust: 0.8

ZDI: CVE-2025-30032
value: MEDIUM

Trust: 0.7

CNVD: CNVD-2025-08353
value: HIGH

Trust: 0.6

CNVD: CNVD-2025-08398
value: HIGH

Trust: 0.6

CNVD: CNVD-2025-08353
severity: HIGH
baseScore: 9.0
vectorString: AV:N/AC:L/AU:S/C:C/I:C/A:C
accessVector: NETWORK
accessComplexity: LOW
authentication: SINGLE
confidentialityImpact: COMPLETE
integrityImpact: COMPLETE
availabilityImpact: COMPLETE
exploitabilityScore: 8.0
impactScore: 10.0
acInsufInfo: NONE
obtainAllPrivilege: NONE
obtainUserPrivilege: NONE
obtainOtherPrivilege: NONE
userInteractionRequired: NONE
version: 2.0

Trust: 0.6

CNVD: CNVD-2025-08398
severity: HIGH
baseScore: 10.0
vectorString: AV:N/AC:L/AU:N/C:C/I:C/A:C
accessVector: NETWORK
accessComplexity: LOW
authentication: NONE
confidentialityImpact: COMPLETE
integrityImpact: COMPLETE
availabilityImpact: COMPLETE
exploitabilityScore: 10.0
impactScore: 10.0
acInsufInfo: NONE
obtainAllPrivilege: NONE
obtainUserPrivilege: NONE
obtainOtherPrivilege: NONE
userInteractionRequired: NONE
version: 2.0

Trust: 0.6

productcert@siemens.com: CVE-2025-30032
baseSeverity: HIGH
baseScore: 8.8
vectorString: CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
attackVector: NETWORK
attackComplexity: LOW
privilegesRequired: LOW
userInteraction: NONE
scope: UNCHANGED
confidentialityImpact: HIGH
integrityImpact: HIGH
availabilityImpact: HIGH
exploitabilityScore: 2.8
impactScore: 5.9
version: 3.1

Trust: 1.0

OTHER: JVNDB-2025-011789
baseSeverity: HIGH
baseScore: 8.8
vectorString: CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
attackVector: NETWORK
attackComplexity: LOW
privilegesRequired: LOW
userInteraction: NONE
scope: UNCHANGED
confidentialityImpact: HIGH
integrityImpact: HIGH
availabilityImpact: HIGH
exploitabilityScore: NONE
impactScore: NONE
version: 3.0

Trust: 0.8

ZDI: CVE-2025-30032
baseSeverity: MEDIUM
baseScore: 6.5
vectorString: AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N
attackVector: NETWORK
attackComplexity: LOW
privilegesRequired: LOW
userInteraction: NONE
scope: UNCHANGED
confidentialityImpact: HIGH
integrityImpact: NONE
availabilityImpact: NONE
exploitabilityScore: 2.8
impactScore: 3.6
version: 3.0

Trust: 0.7

sources: ZDI: ZDI-25-390 // CNVD: CNVD-2025-08353 // CNVD: CNVD-2025-08398 // JVNDB: JVNDB-2025-011789 // NVD: CVE-2025-30032

PROBLEMTYPE DATA

problemtype:CWE-89

Trust: 1.0

problemtype:SQL injection (CWE-89) [ others ]

Trust: 0.8

sources: JVNDB: JVNDB-2025-011789 // NVD: CVE-2025-30032

PATCH

title:Siemens has issued an update to correct this vulnerability.url:https://cert-portal.siemens.com/productcert/html/ssa-443402.html

Trust: 0.7

title:Patch for Siemens TeleControl Server Basic SQL Injection Vulnerability (CNVD-2025-08353)url:https://www.cnvd.org.cn/patchInfo/show/683511

Trust: 0.6

title:Patch for Siemens TeleControl Server Basic has multiple SQL injection vulnerabilitiesurl:https://www.cnvd.org.cn/patchInfo/show/684331

Trust: 0.6

sources: ZDI: ZDI-25-390 // CNVD: CNVD-2025-08353 // CNVD: CNVD-2025-08398

EXTERNAL IDS

db:NVDid:CVE-2025-30032

Trust: 3.9

db:SIEMENSid:SSA-443402

Trust: 3.0

db:JVNid:JVNVU90506697

Trust: 0.8

db:ICS CERTid:ICSA-25-112-01

Trust: 0.8

db:JVNDBid:JVNDB-2025-011789

Trust: 0.8

db:ZDI_CANid:ZDI-CAN-25921

Trust: 0.7

db:ZDIid:ZDI-25-390

Trust: 0.7

db:CNVDid:CNVD-2025-08353

Trust: 0.6

db:CNVDid:CNVD-2025-08398

Trust: 0.6

sources: ZDI: ZDI-25-390 // CNVD: CNVD-2025-08353 // CNVD: CNVD-2025-08398 // JVNDB: JVNDB-2025-011789 // NVD: CVE-2025-30032

REFERENCES

url:https://cert-portal.siemens.com/productcert/html/ssa-443402.html

Trust: 3.7

url:https://jvn.jp/vu/jvnvu90506697/

Trust: 0.8

url:https://nvd.nist.gov/vuln/detail/cve-2025-30032

Trust: 0.8

url:https://www.cisa.gov/news-events/ics-advisories/icsa-25-112-01

Trust: 0.8

sources: ZDI: ZDI-25-390 // CNVD: CNVD-2025-08353 // CNVD: CNVD-2025-08398 // JVNDB: JVNDB-2025-011789 // NVD: CVE-2025-30032

CREDITS

Anonymous

Trust: 0.7

sources: ZDI: ZDI-25-390

SOURCES

db:ZDIid:ZDI-25-390
db:CNVDid:CNVD-2025-08353
db:CNVDid:CNVD-2025-08398
db:JVNDBid:JVNDB-2025-011789
db:NVDid:CVE-2025-30032

LAST UPDATE DATE

2025-08-23T20:42:19.977000+00:00


SOURCES UPDATE DATE

db:ZDIid:ZDI-25-390date:2025-06-16T00:00:00
db:CNVDid:CNVD-2025-08353date:2025-04-25T00:00:00
db:CNVDid:CNVD-2025-08398date:2025-04-25T00:00:00
db:JVNDBid:JVNDB-2025-011789date:2025-08-20T04:40:00
db:NVDid:CVE-2025-30032date:2025-08-19T14:53:32.690

SOURCES RELEASE DATE

db:ZDIid:ZDI-25-390date:2025-06-16T00:00:00
db:CNVDid:CNVD-2025-08353date:2025-04-24T00:00:00
db:CNVDid:CNVD-2025-08398date:2025-04-16T00:00:00
db:JVNDBid:JVNDB-2025-011789date:2025-08-20T00:00:00
db:NVDid:CVE-2025-30032date:2025-04-16T18:16:05.733