ID

VAR-202504-1099


CVE

CVE-2025-32859


TITLE

Siemens TeleControl Server Basic SQL Injection Vulnerability (CNVD-2025-08592)

Trust: 0.6

sources: CNVD: CNVD-2025-08592

DESCRIPTION

A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'LockWebServerGatewaySettings' method. This could allow an authenticated remote attacker to bypass authorization controls, to read from and write to the application's database and execute code with "NT AUTHORITY\NetworkService" permissions. A successful attack requires the attacker to be able to access port 8000 on a system where a vulnerable version of the affected application is executed on. Siemens TeleControl Server Basic is an industrial remote controller of Siemens, Germany

Trust: 1.44

sources: NVD: CVE-2025-32859 // CNVD: CNVD-2025-08592

IOT TAXONOMY

category:['ICS']sub_category: -

Trust: 0.6

sources: CNVD: CNVD-2025-08592

AFFECTED PRODUCTS

vendor:siemensmodel:telecontrol server basicscope:ltversion:v3.1.2.2

Trust: 0.6

sources: CNVD: CNVD-2025-08592

CVSS

SEVERITY

CVSSV2

CVSSV3

productcert@siemens.com: CVE-2025-32859
value: HIGH

Trust: 1.0

CNVD: CNVD-2025-08592
value: HIGH

Trust: 0.6

CNVD: CNVD-2025-08592
severity: HIGH
baseScore: 9.0
vectorString: AV:N/AC:L/AU:S/C:C/I:C/A:C
accessVector: NETWORK
accessComplexity: LOW
authentication: SINGLE
confidentialityImpact: COMPLETE
integrityImpact: COMPLETE
availabilityImpact: COMPLETE
exploitabilityScore: 8.0
impactScore: 10.0
acInsufInfo: NONE
obtainAllPrivilege: NONE
obtainUserPrivilege: NONE
obtainOtherPrivilege: NONE
userInteractionRequired: NONE
version: 2.0

Trust: 0.6

productcert@siemens.com: CVE-2025-32859
baseSeverity: HIGH
baseScore: 8.8
vectorString: CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
attackVector: NETWORK
attackComplexity: LOW
privilegesRequired: LOW
userInteraction: NONE
scope: UNCHANGED
confidentialityImpact: HIGH
integrityImpact: HIGH
availabilityImpact: HIGH
exploitabilityScore: 2.8
impactScore: 5.9
version: 3.1

Trust: 1.0

sources: CNVD: CNVD-2025-08592 // NVD: CVE-2025-32859

PROBLEMTYPE DATA

problemtype:CWE-89

Trust: 1.0

sources: NVD: CVE-2025-32859

PATCH

title:Patch for Siemens TeleControl Server Basic SQL Injection Vulnerability (CNVD-2025-08592)url:https://www.cnvd.org.cn/patchInfo/show/684191

Trust: 0.6

sources: CNVD: CNVD-2025-08592

EXTERNAL IDS

db:SIEMENSid:SSA-443402

Trust: 1.6

db:NVDid:CVE-2025-32859

Trust: 1.6

db:CNVDid:CNVD-2025-08592

Trust: 0.6

sources: CNVD: CNVD-2025-08592 // NVD: CVE-2025-32859

REFERENCES

url:https://cert-portal.siemens.com/productcert/html/ssa-443402.html

Trust: 1.6

sources: CNVD: CNVD-2025-08592 // NVD: CVE-2025-32859

SOURCES

db:CNVDid:CNVD-2025-08592
db:NVDid:CVE-2025-32859

LAST UPDATE DATE

2025-04-28T19:42:32.222000+00:00


SOURCES UPDATE DATE

db:CNVDid:CNVD-2025-08592date:2025-04-28T00:00:00
db:NVDid:CVE-2025-32859date:2025-04-17T20:21:48.243

SOURCES RELEASE DATE

db:CNVDid:CNVD-2025-08592date:2025-04-28T00:00:00